(15KVA - 25KVA) 3P OFF GRID HYBRID INVERTER
Our USP:
| Bi Directional | Seamless switching to and from grid (both import and export) and battery supply, high-efficiency MPPT technology |
| GRID-INTERACTIVE | Blends solar and grid- power for optimisation |
| IEC CERTIFIED | IEC certifications available |
| PURE SINE WAVETECHNOLOGY | Recommended for longer life of Industrial/Commercial equipment |
| INTELLIGENT BATTERYCHARGING | 3-Stage charging (Float, Bulk & Absorption) for more battery life (for Lead Acid batteries). Communication-based charging for Lithium chemistries available |
| COMPATIBLE CHARGER Supports | Supports wide range of batteries-Flooded Lead Acid Tubular/GEL/VRLA. Onrequest product for Li+ |
PRONTO RENEWABLES ENERGY PVT LTD | ||||||
| PRONTO 3P SOLAR OFF GRID/HYBRID INVERTER - SPECIFICATIONS | ||||||
| INVERTER RATING (KVA) | 15KVA | 15KVA | 20KVA | 20KVA | 25KVA | |
| BATTERY VOLTAGE | 120V | 240V | 120V | 240V | 240 | |
| SOLAR CHARGE CONTROLLER | TECHNOLOGY-MPPT/VOC RANGE 140-400V | TECHNOLOGY-MPPT/VOC RANGE 275-700V | TECHNOLOGY-MPPT/VOC RANGE 140-400V | TECHNOLOGY-MPPT/VOC RANGE 275-700V | TECHNOLOGY-MPPT/VOC RANGE 275-700V | |
| A | SOLAR CHARGE CONTROLLER | |||||
| 1 | Charger Type & Topology | Buck Type MPPT | ||||
| 2 | PV Total Nominal Capacity (KW) | 15 KW | 15KW | 20KW | 20KW | 25KW |
| 3 | Per Channel PV Capacity (w)(Nominal Peak) | 15KW/16.5KW | 15KW/16.5KW | 20KW/22KW | 20KW/22KW | 25KW/27.5KW |
| 4 | PV Minimum Voltage (Volts) | 140 | 275 | 140 | 275 | 275 |
| 5 | Max. I/P Amps per channel (Amps) | 90 | 45 | 90 | 60 | 65 |
| 6 | Max. Battery Amps during PV charging | 95 | 47 | 120 | 60 | 60 |
| 7 | Battery type Supported | VRLA / LMLA / Li-ion/ LiFePo4 (User Settable) | ||||
| 8 | Min. Battery AH (Suggested) | 300 | 300 | 300 | 300 | 300 |
| 9 | Peak charging Efficiency MPPT (%) | >93% | >93% | >93% | >93% | >93% |
| A.1 | MPPT Charger Controller | |||||
| 1 | No. Of MPPT Channels | 1 | 1 | 1 | 1 | 1 |
| 2 | Max.Open Circuit PV Volts (Voc) MPPT | 400 | 700 | 400 | 700 | 700 |
| 3 | MPPT Voltage Range (Volts) | 140-400 | 275-700 | 140-400 | 275-700 | 275-700 |
| 4 | Max. SCC O/P (Amps) | 95 | 47 | 120 | 60 | 60 |
| B | SOLAR INVERTER | |||||
| 1 | No. of Phases/Connection Type | 3Phase/4 wire | ||||
| 2 | Nominal KW Capacity (KW) (Tortal Per Phase)(*4) | 12.0/4.0 | 12.0/4.0 | 16.0/5.33 | 16.0/5.33 | 20.0/6.66 |
| 3 | Nominal Battery Voltage | 120 | 240 | 120 | 240 | 240 |
| 4 | Nominal Output Voltage/ Frequency (Volts/Hz) | 415/50 | 415/50 | 415/50 | 415/50 | 415/50 |
| 5 | Output Amp per Phase (*4) | 17.4 | 17.4 | 23.17 | 23.17 | 28.9 |
| 6 | Voltage Regulation (in Standalone Mode) | ± 2% | ± 2% | ± 2% | ± 2% | ± 2% |
| 7 | Freq. Regulation (in Standalone Mode) | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz |
| 8 | THD | <3% | <3% | <3% | <3% | <3% |
| 9 | Load Power Factor | 0.8 lag to unity | ||||
| 10 | Efficiency (%): Peak/ 100% Load/25% Load | >89/ >88/ >80 | >92/ >90/ >85 | >89/ >88/ >80 | >92/ >90/ >85 | >92/ >90/ >85 |
| 11 | Over Loads : | 100-110% - 60 sec | ||||
| 12 | 110-125% - 30 sec | |||||
| 13 | 125-150% - 5 sec | |||||
| 14 | Max Alowed Phase Imbalnce (%) | 100% | 100% | 100% | 100% | 100% |
| 15 | Auto Bypass Feature | Provided | Provided | Provided | Provided | Provided |
| 16 | Parallel Operation with grid/DG | Provided | Provided | Provided | Provided | Provided |
| 17 | Power Export to Grid Facility Enable/Disable) | Enable/Disable (User Settable) | ||||
| 18 | Anti Islanding from Grid | Provided | Provided | Provided | Provided | Provided |
| C | GRID CHARGER | |||||
| 1 | Grid Voltage Range (Voltage Sync. Range) | 160V-280V (Phase to Neutral) | ||||
| 2 | Grid Frequency Range (Freq. Sync. Range) | 50 Hz ± 5% | ||||
| 3 | Max. Grid Import Power (KW) | 12KW | 12KW | 16KW | 16KW | 20KW |
| 4 | Peak charging Efficiency (%) | >87 | >87 | >87 | >87 | >87 |
| 5 | Max Battery Amps During Grid Charging (Amps) | 70 | 35 | 95 | 47 | 75 |